E PA / H E PA / U L PA F i l t e r s : E 1 0 t o U 1 7
H EPA / U L PA P a n e l s
Silent Hood filter MD14-HL
Advantages
• H14 compact filter-diffuser
• Quiet: LW = 35 dB
for clean room
• Ready to install
• Laminarity +/- 20%
d
H
TIFICAT
ER
E
C
W
As part of our program for continuous improvement, Camfil reserves the right to change specifications without notice. 2015-01-15
EN 1822
D
D
Application: Final filtration for clean rooms.
Type: Ready to install HEPA/ULPA filter diffuser.
Frame: Extruded and anodised aluminium, galvanised steel cover.
Gasket: Half round continuous expanded polyurethane.
Media: Glass fiber paper.
Separator: Hot melt beads.
Sealant: Polyurethane.
Connection: Spigot with outer dia. 315mm or 250mm depending on the model.
Grid: Expanded metal on downstream side, powder coated with RAL 9010.
Fiilter class acc. EN1822:2009: H14.
MPPS efficiency: ≥99.995%.
Recommended final pressure drop: 2x initial pressure drop
Maximum pressure drop: 500 Pa.
Maximum flow rate: use nominal values otherwise a reduction in efficiency may occur. (See
table)
Temperature: 70ºC maximum in continuous service.
Test: 100% individually scanned in accordance with EN 1822.
Mounting system: Mechanical clamping structures.