Definite Purpose Contactors
1, 2 and 3 pole
Type GDP
l Definite
Purpose Contactors
up to 100A resistive, 90A inductive
l Line Voltage up to 600VAC on most sizes
l Control voltage up to 480VAC
l Screw or box lug terminals available on most sizes
l Fast-on coil and power terminal
l Hp ratings on 3-pole contactors
l UL recognized for US and Canada
l Cost effective
l Switching
Product Description
Ordering Key GDP 401 S L 120V 01
Power contactors specifi- welders, etc. Available in
cally designed for the OEM standard 1, 2 and 3-pole
when contactor, perfor- type.
mance and cost must be
optimized. Perfect choicefor HVAC, lighting, pumps,
compressors, pools, spas,
Product Series
Amperage Rating
Number of Poles
Optional Shunt
Load Terminals
Coil Voltage
Position of Coil Terminals
Auxiliary Output
Type Selection
Product Series
Amperage Rating
Number of Poles
Optional Shunt
Load Terminals
GDP
25: 25 Amps
32: 32 Amps
40: 40 Amps
50: 50 Amps
60: 60 Amps
75: 75 Amps
90: 90 Amps
1: 1 Pole
2: 2 Poles
3: 3 Poles
S:
With Shunt
Blank: No Shunt
L: Lug*
S: Screw**
Coil
Voltage
Position of Coil
Terminals
(3-pole only)
Auxiliary
Output
24V: 24 VAC
120V: 110/120 VAC
220V: 220 VAC
277V: 277 VAC
480V: 480 VAC
Blank: bottom
T: top
01: 1 NC***
Blank: none
* Lug and Fast-On load termianals.
Fast-on control terminals
** Screw and Fast-On load termianals.
Fast-on control terminals
*** Available only on 1 Pole contactors
See page x for list of available part numbers
Specifications are subject to change without notice — October 24, 20151
GDP
Selection Guide
Amperage
Terminal
Rating
Type
Screw
25 Amps
Lug
Screw
32 Amps
Lug
Screw
40 Amps
Lug
50 Amps
Lug
60 Amps
Lug
75 Amps
Lug
90 Amps
Lug
Coil 1 Pole
1 Pole
2 Pole
3-Pole
Voltage
with 1 Aux
with shunt
24 VAC
GDP251S24V01
GDP251SS24V
GDP252S24V GDP253S24V
120 VAC
GDP251S120V01
GDP251SS120VGDP252S120V GDP253S120V
220 VAC
GDP251S220V01
GDP251SS220V
GDP252S220V GDP253S220V
277 VAC
GDP251S277V01
GDP251SS277V
GDP252S277V GDP253S277V
480 VAC
GDP251S480V01
GDP251SS480V
GDP252S480V GDP253S480V
24 VAC
GDP251L24V01
GDP251SL24V
GDP252L24V GDP253L24V
120 VAC
GDP251L120V01
GDP251SL120V
GDP252L120V GDP253L120V
220 VAC
GDP251L220V01
GDP251SL220V
GDP252L220V GDP253L220V
277 VAC
GDP251L277V01
GDP251SL277V
GDP252L277V GDP253L277V
480 VAC
GDP251L480V01
GDP251SL480V
GDP252L480V GDP253L480V 24 VAC
GDP321S24V01 GDP321SS24V GDP322S24V GDP323S24V
120 VAC
GDP321S120V01
GDP321SS120V GDP322S120V GDP323S120V
220 VAC
GDP321S220V01
GDP321SS220V GDP322S220V GDP323S220V
277 VAC
GDP321S277V01 GDP321SS277V GDP322S277V GDP323S277V
480 VAC
GDP321S480V01 GDP321SS480V GDP322S480V GDP323S480V
24 VAC
GDP321L24V01 GDP321SL24V GDP322L24V GDP323L24V
120 VAC
GDP321L120V01
GDP321SL120V GDP322L120V GDP323L120V
220 VAC
GDP321L220V01
GDP321SL220V GDP322L220V GDP323L220V
277 VAC
GDP321L277V01 GDP321SL277V GDP322L277V GDP323L277V
480 VAC
GDP321L480V01 GDP321SL480V GDP322L480V GDP323L480V
24 VAC
GDP401S24V01
GDP401SS24V GDP402S24V GDP403S24V
120 VAC
GDP401S120V01
GDP401SS120V GDP402S120V GDP403S120V
220 VAC
GDP401S220V01
GDP401SS220V GDP402S220VGDP403S220V
277 VAC
GDP401S277V01 GDP401SS277V GDP402S277V
GDP403S277V
480 VAC
GDP401S480V01
GDP401SS480V GDP402S480V
GDP403S480V
24 VAC
GDP401L24V01
GDP401SL24V GDP402L24V GDP403L24V
120 VAC
GDP401L120V01
GDP401SL120V GDP402L120V GDP403L120V
220 VAC
GDP401L220V01
GDP401SL220V GDP402L220VGDP403L220V
277 VAC
GDP401L277V01 GDP401SL277V GDP402L277V
GDP403L277V
480 VAC
GDP401L480V01
GDP401SL480V GDP402L480V
GDP403L480V
24 VAC
GDP503L24V
120 VAC
GDP503L120V
220 VAC
GDP503L220V
277 VAC
GDP503L277V
480 VAC
GDP503L480V
24 VAC
GDP603L24V
120 VAC
GDP603L120V
220 VAC
GDP603L220V
277 VAC
GDP603L277V
480 VAC
GDP603L480V
24 VAC
GDP753L24V
120 VAC
GDP753L120V
220 VAC
GDP753L220V
277 VAC
GDP753L277V
480 VAC
GDP753L480V
24 VAC
GDP903L24V
120 VAC
GDP903L120V
220 VAC
GDP903L220V
277 VAC
GDP903L277V
480 VAC
GDP903L480V
Part numbers in bold font indicate stock code A items. All other part numbers are stock code D.
Specifications are subject to change without notice — October 24, 20152
GDP
Technical Specifications
1 Pole
Voltage
FLA
LRA
Horsepower
Resistive Rating
240/27725
150 -
32
240/27732
200 -
40
240/27740
240 -
50
2 Pole
240/27725
150 -
32
GDP252480
20120
- 32
60015 90 - 32
240/27732
200 -
40
GDP322480
25150
- 40
60020 120 - 40
240/27740
240 -
50
GDP402480
32200
- 50
60025 160 - 50
3Pole
240/27725
150 7.5
32
GDP253480
20110
10 32
60015 90 10 32
240/27732
200 10
40
GDP323480
25115
15 40
60020 95 15 40
240/27740
240 10
50
GDP403480
32150
20 50
600 25 12020 50
240/27750
300 15
60
GDP503480
40215
30 60
600 32 17530 60
240/27760
360 20
75
GDP603480
40215
30 75
600 32 17530 75
240/27775
450 25
90
GDP753480
60375
50 90
600 50 30050 90
240/27790
540 30
100
GDP903480
75450
60100
600 60 36060 100
Model
GDP251
GDP321
GDP401
Coil Specifications
Model
All 1P and 2P
In-rush VA
55
GDP253 ~ GDP40351
GDP503 ~ GDP603
83
GDP753 ~ GDP903
165
Uc - nominal coil voltage
1 Pole and 2 Pole Contactors
Sealed VA
Operational Voltage Drop-out Voltage
Frequency
13
(85%~110%) Uc
(20% ~ 65%) Uc
50 / 60 Hz
3 Pole Contactors
12
14
(85%~110%) Uc
(20% ~ 65%) Uc
50 / 60 Hz
30
Specifications are subject to change without notice — October 24, 20153
GDP
Enviromental Specification
l
l
l
l
l
l
l
Operating Temperature:
Temperature ≤35°C in 24h period.
-5 ~ 40°C (+23 ~ 104°F) - full current rating.
41 ~ 50°C (106 ~ 122°F) - 0.875 de-rating factor
51 ~ 60°C (124 ~ 140°F) - 0.750 de-rating factor
61 ~ 70°C (142 ~ 158°F) - 0.625 de-rating factor
Storage Temperature: -25 - +55°C (-13 ~ 131°F)
Relative Humidity: less than 50% @40°C, non-condensing
Shock and Vibration: do not subject product to shock and vibration
Pollution Degree: 2
Altitude: ≤2000m
Installation: ≤5° from vertical plane
Agency Approvals, Conformance
l
Agency approvals: UL file: E236208, UL category: NLDX2, NLDX8
SCCR rating: 5K rms symmetrical Amperes, 600V max, when protected by UL listed fuse
l CE: EN 60947-4-1:2010+A1
l Utilization categories: AC-1, AC-8a
l Environmental: RoHS
l
Connection Diagrams
1 Pole with 1 auxiliary contact
GDP251…01, GDP321..01, GDP401..01
A1
A1
A2
1/L1
11 1/L1
A1
1/L1
11 1/L1
A1
11
11
A2
A1
A1
A2
1 Pole with shunt
GDP251, GDP321, GDP401
1/L1
N 1/L1
A1
1/L1
N 1/L1
A1
N
N
A2
2/T1 A2 12 2/T1
12
2/T1 A2
N 2/T1
N
2A2
Pole 3
Pole
A2
2/T1 GDP402
12 2/T1
12
2/T1GDP253,
N 2/T1
N
GDP252, GDP322,
GDP323, GDP403
GDP503, GDP603, GDP753, GDP903
A1
A1
1/L1 3/L2 1/L1
A1
1/L1 3/L2 1/L1
A1
3/L2
3/L2
A2
A2
A2
2/T1 A24/T2 2/T1
2/T1 4/T2 2/T1
4/T2
4/T2
A1
A1
1/L1 3/L2 1/L1
5/L3 3/L2
A1
1/L1 3/L2 1/L1
5/L3 3/L2
A1
A2
A2
A2
2/T1 A24/T2 2/T1
6/T3 4/T2 6/T3
2/T1 4/T2 2/T1
6/T3 4/T2 6/T3
5/L3
5/L3
1/L1, 2/T1, 3/L2, 4/T2, 5/L3, 6/T3 are the main power contacts
11, 12 are low current Normally Closed auxiliary contacts
A1, A2 are coil contacts
Specifications are subject to change without notice — October 24, 20154
GDP
Auxiliary Contact Specifications
For 1 Pole Contactors with 01 sufix
Ith (A)
Ui (V)
AC (VA)
10600 300
DC (W)
30
Terminal Connections:
Power Terminals
Contactor Series
Screw Type
Max wire size AWG [mm2]
Max torque value Terminal Type
and Size
Stranded Solid
lb-in [N-m]
GDP251S
Screw
Phillips, M5
14-12 [2.5~4]
14-10 [2.5~6]
GDP251L
Lug
Flat head, M8
14-12 [2.5~4]
14-10 [2.5~6]
20 [2.2]
GDP252S, GDP32S, GDP40S
Screw
Phillips, M5
use ring of fork terminals only
GDP252L, GDP32L, GDP40L
Flat head, M8
14-10 [2.5~6]
12-8 [4~10]
GDP503L, GDP603L
Lug
Flat head, M10
12 -8 [4~10]
10-6 [6~16]
40 [4.5]
GDP753L, GDP903L
Flat head, M12
6-4 [ 16~25]
4-3 [25~35]
50 [5.6]
All power terminals offer additional dual 1/4” fast-on terminals
60/75C cupper wire only
Coil terminals
Contactor Series
Screw Type Max wire size
Max torque value
Terminal Type
and Size
AWG [mm2]
Lb-in [N-m]
GDP251S
GDP251L
Dual 1/4” fast-on
N/A
N/A
N/A
GDP252S, GDP32S, GDP40S
GDP252L, GDP32L, GDP40L
GDP503L, GDP603L
Dual 1/4” fast-on Phillips, M4
16 - 14 [1~2.5]
10 [1.2]
GDP753, GDP903L
plus screw
Auxiliary Contacts
Contactor Series
Screw Type Max wire size
Max torque value
Terminal Type
and Size
AWG [mm2]
Lb-in [N-m]
GDP251S
Screw
Phillips, M4
16 - 14 [1~2.5]
10 [1.2]
GDP251L
Endurance Ratings
Rating Type
Mechanical life of the contactor
UL508 electrical life of contacts
Product
Rating
All 1Ppole and 2Pole
1 million cycles
All 3Pole
500K cycles
All
30K cycles
Accessories
GNCF8-11: Snap-on auxiliary contact block for 3 pole contactors. 1NO/1NC, Ith= 10A, screw terminals
Specifications are subject to change without notice — October 24, 20155
GDP
Dimensions:
55max
4x dia. 5.2mm
4x dia. 5.2mm
5.2
92max
41.3±0.2
45±0.2
67max
22.2±0.14
41.3±0.2
R
92max
22±0.14
41.3±0.2
5.2
R
41.3±0.2
67max
55max
45±0.2
GDPx1S
(1 pole +(1AUX)
and GDPx2and
(2 pole)
GDPx1S
pole+AUX)
GDPx2 (2 pole)
GDPx1 (1 pole+shunt)
GDPx1 (1 pole + shunt)
68.5max
51.7±0.2
37.5±0.2
5.5
68.5max
57±0.2
5.5
5.5
5.5
5.5
5.5
5.5
82.5±0.25
79.2±0.25
79.2±0.25
82.5±0.25
96max
116.5max
5.5
1.6
75max
5.5
37.5±0.2
57±0.2
81max
37.5±0.2
51.7±0.2
GDP203
~ GDP403
pole 20~40A)(3 pole 20~40A)
GDP203
~ (3GDP403
GDP503
~ GDP603 (3 ~
poleGDP603
50~60A)
GDP503
(3 pole 50~60A)
117±0.18
135max
5
74±0.18
64±0.18
+0.14
0
8
10
90.5max
5
+0.14
0
117max
GDP753 ~ GDP903
(3 pole 75~90A)
GDP753
~ GDP903
(3 pole 75~90A)
All Dimensions are expressed in millimeters
Specifications are subject to change without notice — October 24, 20156