Energy Measuring Unit
Energy
Saving
Preventive
Maintenance
Energy measuring +α
Energy Saving + Preventive Maintenance
Providing energy visualization and More!
Introducing the EcoMonitorPlus, an energy measuring units
that visualize "energy" to respond to a wide range of customer needs such
as monitoring of power consumption, configuration of an energy-saving system,
and stable operation of equipment.
The EcoMonitorPlus is suitable if you are thinking
Want to expand the energy-saving
system in phases.
At first, use the EcoMonitorPlus to obtain measurements at locations you are concerned about. Then,
when a need to increase the number of measuring
points arises, add measuring, logging and communication units as needed.
Want to manage data measured at
specific locations easily and use the data
to check energy-saving effects.
The logging unit lets you collect measurement data
via SD memory card. Using the documentation
software, you can easily manage data and create
graphs from data.
Product Lineup
Features
Specifications
Names of Parts and
External view
External view
By using the insulation monitor unit and measuring
leakage current, you can ensure stable operation of
equipment and utilize data for preventive maintenance.
P3
2. Features
P6
3. Specifications
P9
4. Names of Parts and External view
P15
5. External view
P17
6. Connection Configurations
P20
7. Simplified Comparison of
EcoMonitor Prod
P22
Simplified Comparison of
EcoMonitor Prod
Want to use the EcoMonitorPlus not only
for saving energy
but also for other purposes.
1. Product Lineup
Connection
Configurations
about the following!
C o n t e n t s
1. Product Lineup
Product Lineup
Energy Measuring Unit (Basic Unit)
* Photos are full-scale
External view
Names of Parts and
External view
Specifications
Features
Three types of basic measuring unit*1 are available.
You can select the most suitable model according to the application.
EMU4-BM1-MB
EMU4-HM1-MB
EMU4-LG1-MB
Energy Measuring
Standard Model
Energy Measuring
High Performance Model
Insulation Monitor Model
EMU4-BM1-MB
EMU4-HM1-MB
EMU4-LG1-MB
Suitable for visualization
In addition to the functions of
the Standard Model, this model comes
with additional functions
for the measurement of 3-phase 4-wire
and pulse count.
Capable of Measuring
of "energy" in a simple way!
Connection
Configurations
① Equipped with basic functions for
monitoring of voltage, current,
power and electric energy.
② Standard-equipped with
MODBUS® RTU communication.
① Same basic functions as the
Standard Model.
② Standard-equipped with
MODBUS® RTU communication.
③ Three-phase 3-wire,440V direct
voltage input is available.
④ Three-phase 4-wire, 270V/480V
Leakage Current.
① Measurement of leakage current.
② Equipped with a MODBUS® RTU
communication function.
③ Capable of measuring Ior (resistive
leakage current).
④ Equipped with alarm functions.
direct voltage input is available.
Simplified Comparison of
EcoMonitor Prod
⑤ Capable of displaying harmonic
3
current, voltage, apparent power,
periodic electric energy and
electric energy conversion value.
Product name
Energy Measuring Unit
[Energy Measuring Standard Model]
Product name
Energy Measuring Unit
[Energy Measuring High Performance Model]
Product name
Energy Measuring Unit
[Insulation Monitor Model]
Model
EMU4-BM1-MB
Model
EMU4-HM1-MB
Model
EMU4-LG1-MB
*1 Basic unit cannot be used as an extension unit.
Product Lineup
Energy Measuring Unit (Extension Unit*1*2)
Two types of extension energy measuring unit are available.
You can select the most suitable model according to your need, such as
measurement of same voltage or measurement of different voltages.
Features
Energy Measuring
Extension Unit for Different Voltage System
Energy Measuring
Extension Unit for Same Voltage System
EMU4-VA2
EMU4-A2
For measurement of circuits
For measurement of circuits
of different voltages
of same voltage
① Measurement of two circuits (per unit).
② Capable of producing as many contact or pulse outputs as
the number of circuits (selectable for each circuit).
③ Measurement of different transformer system by each unit
(capable of measuring voltage different from that
measured by the unit connected on the left side).
① Measurement of two circuits (per unit).
② Capable of producing as many contact or pulse outputs as
the number of circuits (selectable for each circuit).
③ Connection wiring for voltage not necessary for measure-
ment of same voltage (capable of measuring same voltage
that measured by the unit connected on the left side).
Energy Measuring Unit
[Energy Measuring Extension Unit for Different Voltage System]
Product name
Energy Measuring Unit
[Energy Measuring Extension Unit for Same Voltage System]
Model
EMU4-VA2
Model
EMU4-A2
External view
Product name
Names of Parts and
External view
EMU4-A2
Specifications
EMU4-VA2
*1 Up to three extension units can be connected.
*2 Each extension unit can measure two circuits, but the circuits must be of the same voltage system. Different voltage system cannot be measured.
■ Optional Units
Units**1
Connection
Configurations
EMU4-CM-C
For CC-Link communication
Product name
Logging unit
Model
EMU4-LM
*1 One basic unit can be connected with one optional unit.
Product name CC-LINK communication unit
Model
EMU4-CM-C
Simplified Comparison of
EcoMonitor Prod
EMU4-LM
For customers who want to easily manage
data using SD memory cards!
4
1. Product Lineup
Product Lineup
■ Option
Split-type Current Sensor
Features
Product name
Specifications
Split-type current
sensor
Model
Options for 5A Current Sensor (Current Sensor Cable)
External view
UL compatibility
Product name
Model
External view
EMU2-CB-Q5A
EMU-CT5-A
×
EMU-CT50-A
×
EMU-CT100-A
×
EMU-CT-250-A
×
EMU-CT400-A
○
EMU2-CB-T1M(1m)
Extension cable
EMU2-CB-T5M(5m)
(Standard type)
EMU2-CB-T10M(10m)
EMU-CT600-A
○
EMU2-CB-T1MS(1m)
Extension cable
EMU2-CB-T5MS(5m)
(Separate type)
EMU2-CB-T10MS(10m)
EMU-CT50
○
EMU-CT100
○
EMU-CT250
○
EMU2-CT5
○
EMU2-CT5-4W
○
5A Current
sensor cable
(Single-phase 2-wire, single-phase
3-wire and three-phase 3-wire)
EMU2-CB-Q5A-4W
(Three-phase 4-wire )
Names of Parts and
External view
*1 Use commercially available cables for the connection of current sensors.
Compatible cable: AWG22-14
(Single wire: φ0.65 to φ1.62 mm2, Stranded wires: φ0.33 to φ2.0 mm2)
*2 Current sensor cable can be extended up to 50 m.
For the 5A current sensor (EMU2-CT5,EMU2-CT5-4W), cable can be extended to 10.5 m.
*3 In divided split-type Current Sensor (EMU2-CT5(4W)) usa, EMU2-CB-Q5A(4W) is needed.
Zero-phase Current converter
Product name
Compact Display Unit
Model
External view
Split-type zero-phase
current converter
CZ-30S
CZ-55S
CZ-112S
External view
Through-type
zero-phase
current converter
ZT30B
ZT60B
ZT100B
Zero-phase current
transformer with
primary conductor
Connection
Configurations
External view
Compact display unit
EMU4-D65
Compact display unit
connecting cable
EMU2-CB1-DP
Compact display unit
power cable
EMU4-CB-DPS
ZT40B
ZT80B
Simplified Comparison of
EcoMonitor Prod
Model
CZ-77S
ZT15B
5
Product name
CZ-22S
ZTA600A
ZTA1200A
* See the external view.
ZTA2000A
Optional Parts for Logging Unit
Product name
Model
SD memory card
for logging unit
EMU4-SD2GB
Lithium battery
for logging unit
EMU4-BT
*1 Each logging unit is supplied with one lithium battery (EMU4-BT).
External view
*1 Commercially available DC power supply units are required for the connection of multiple
EMU4-D65 units.
Compatible product: Cosel PBA15F-9-N1.
*2 Compact display unit connecting cables are required for the connection of multiple display
units.
*3 Up to seven compact display units can be connected.
2. Features
Product Lineup
Want to expand the energy-saving system in phases!
■You can start measurement at locations where you want to achieve energy saving.
■Expanding the system by adding more units as the number of measurement circuits increases.
Maximum
Optional unit
1 circuit
2 circuits
2 circuits
2 circuits
Basic unit
Extension unit
Extension unit
Extension unit
Features
Number of measurement circuits
14 circuits (Singie-phase 2-wire)
7 circuits (Single-phase 3-wire,three-phase 3-wire,three-phase 4wire)
Specifications
Names of Parts and
External view
Basic unit cannot be used as an extension unit.
Up to three optional units can be connected.
On basic unit can be connected with only one optional unit.
Want to use various functions!
External view
440V direct measurement
Conversion of electric energy to other units
Display of electricity fee
VT not necessary
* Applicable to EMU4-HM1-MB, EMU4-LG1-MB and EMU4-VA2.
Test function for equipment communication
and output check
Measured electric energy can be converted and
displayed in another unit of measurement.
* The unit of display value can be selected from none, Wh, kWh, MWh, J, m2,
m3, L, kL, sec, min, hour, pieces, units, g, kg, t, ¥ and $.
Measurement of
up to four different systems
Pulse/alarm output
By supplying auxiliary power (voltage/current input not
necessary), alarm/pulse test signal and communication
test data for host system can be output for the confirmation of proper equipment operation.
Light
Air conditioner
By adding Energy Measuring Extension Unit for
Different Voltage System, a different transformer
system can be measured by each unit.
Simplified Comparison of
EcoMonitor Prod
Communication check
Connection
Configurations
No VT necessary for voltage input
Space-saving installation to panel, reduced cost.
6
2. Features
Product Lineup
Want to create reports and graphs for simplified
management of measurement data!
Easy collection of measurement data using SD memory card
Features
■Using the logging unit, you can collect data without a host application program such as a PC-based
application.
■Documentation software(Logging Unit Utility)enables easy creation of reports and graphs.
Specifications
Logging Unit Utility
Names of Parts and
External view
Logging Unit Utility carries out free download, and gets
from the “design supportive tool data” of the Mitsubishi Electric web site
energy saving supportive equipment menu.
①Measurement
②Logging
③Document production
Sample of report
2015/4/20
Electric energy Electric energy Electric energy Electric energy Electric energy Electric energy Electric energy
(consumption) (consumption) (consumption) (consumption) (consumption) (consumption) (consumption)
Time
CH7 Electric energy (consumption) [kWh]
CH6 Electric energy (consumption) [kWh]
CH5 Electric energy (consumption) [kWh]
External view
CH4 Electric energy (consumption) [kWh]
CH3 Electric energy (consumption) [kWh]
CH2 Electric energy (consumption) [kWh]
CH1 Electric energy (consumption) [kWh]
Simplified Comparison of
EcoMonitor Prod
Connection
Configurations
Daily total
Daily maximum
Daily minimum
Daily average
7
MODBUS® RTU (RS-485) communication function for
maximum use of data acquisition software
■Providing MODBUS® RTU(RS-485) communication as standard equipment allows
you data collection and report production by using software free(*1).
Converter*2*3
EcoMonitorPlus
*1 Data acquisition software carries out free download, and gets from the “design supportive tool data” of the Mitsubishi
Electric web site energy saving supportive equipment menu.
*2 Used converter can be a LAN ⇔ RS-485 converter or USB ⇔ RS-485 converter.
*3 Connectable devices: LINEEYE SI-65 (LAN ⇔ RS-485 converter) and LINEEYE SI-35USB (USB ⇔ RS-485 converter).
Product Lineup
Want to use the EcoMonitorPlus for purposes
other than energy saving!
Monitoring of leakage current and load current
< Measurement of leakage current >
Features
①Capable of measuring even extremely low levels of leakage current.
Insulation monitor unit (EMU4-LG1-MB)Leakage current resolution: 0.01 mA
⇒Capable of measuring leakage current in equipment groups, such as motors.
②Monitoring of equipment insulation degradation using Ior system
Since leakage current (Io)is affected by the Ioc of the whole equipment,
the Ior measurement is effective for insulation deterioration diagnosis.
■Method of leakage current measurement(Io and Ior measurements)
Specifications
Ioc fluctuates on equipment with long wiring distance
or inverter devices and filters.
Tr
Ioc
{
Io
Io
Ior
Capacitor
Ior
Ioc
Resistance
Ioc
When Ioc is low
=
Ior
Amount of chance due
to insulation deterioration
Ioc
Io
Io’
Io’
Ior
Amount of
change in Io
Io
Ioc
Ior’
≒
Ior
Amount of
change in Ior
Amount of
change in Io
<
Ior’
Amount of
change in Ior
< Measurement of load current >
Alarm output + Current upper-/lower-limit monitoring
Alarm output
Using the contact output and current upper-/lower-limit monitoring
function, the EcoMonitorPlus can detect abnormalities of production
equipment before a problem actually occurs.
Names of Parts and
External view
Ior : Leakage current (resistive leakage current) which flows due
to degraded insulation
Ioc: Leakage current (leakage current from electrostatic capacity)
which flows even if the insulation condition is sound
Io : Composite leakage current of Ior and Ioc (composition of vectors)
When Ioc is high
EMU4-HM1-MB
External view
Production
equipment
Application example
■Monitoring of load/leakage current in emulsification/dispersion/dissolution equipment
of beverage production line.
Solution
Using the basic unit and extension unit to set the threshold values
for electric leakage and load current, preventive maintenance/
repair can be conducted before an equipment problem occurs so
that unexpected equipment shutdown can be prevented.
Control panel
Split-type
current sensor
Basic unit
Extension unit
Equipment has been operating at high
operating rates for more than 10 years,
so failure may occur anytime unexpectedly.
Motor
Output an alarm
when the threshold
is exceeded.
What EcoMonitorPlus
can do
It measures leakage current and
load current for predictive monitoring of
problems due to insulation degradation or
aged deterioration of motor, thus helping
prevent unexpected equipment failure.
Reduction of equipment
repair expenses and improvement
of production efficiency.
Simplified Comparison of
EcoMonitor Prod
GOT for
visualization of load/
leakage current.
Connection
Configurations
Problem
Heat seizure occurred in the motor for
equipment due to electrical leakage.
Line stopped operating, resulting in a decline of production efficiency.
Repair of the motor costs several million yen!
8
3. Specifications
Energy Measuring Unit
Product Lineup
■Basic Unit
Item
Specification
Energy Measuring Standard Model
EMU4-BM1-MB
Model
Energy Measuring High Performance Model
EMU4-HM1-MB
Insulation Monitor Model
EMU4-LG1-MB
Single-phase 2-wire/single-phase 3-wire,
Single-phase 2-wire/single-phase 3-wire,
Single-phase 2-wire/single-phase 3-wire,
3-phase 3-wire common
3-phase 3-wire/ three-phase 4-wire common 3-phase 3-wire/ three-phase 4-wire common
Single-phase 2-wire/
110V, 220V AC common (*1)
110V, 220V, 440V AC common (*2) 110V, 220V, 440V AC common (*11)
3-phase 3-wire
wires 1 and 2, and wires 2 and 3),
110V AC (between wires 1 and 2, and wires 2 and 3),
Voltage
Single-phase 110V AC (between wires 1 and 2, and wires 2 and 3), 110V AC (between
220V AC (between wires 1 and 3)
220V AC (between wires 1 and 3)
220V AC (between wires 1 and 2, and wires 2 and 3),
220V AC (between wires 1 and 2, and wires 2 and 3),
3-wire
circuit
220V AC (between wires 1 and 3)
440V AC (between wires 1 and 3)
440V AC (between wires 1 and 3)
ー
3-phase 4-wire
Minimum: 63.5V/110V AC, Maximum: 277V/480V AC (*3) Minimum: 63.5V/110V AC, Maximum: 277V/480V AC(*12)
Phase wire system
Instrument
ratings
Features
Current circuit
50A, 100A, 250A, 400A, 600A
(Dedicated split-type current sensor is used. All values indicate primary current values of current sensor.)
5A
(Dedicated 5A current sensor is used. Current transformer (CT) is used in two-step configuration together with the
5A current sensor in order to allow a maximum primary current value setting of 30,000A) (*4)
1A
(Mitsubishi ZCT is used. Primary
current value of ZCT is indicated.)
Specifications
Frequency
50/60Hz (automatic frequency selection)
100V – 240V AC (+10%, -15%) 50/60Hz
Auxiliary power rating
1 circuit
No. of measurement circuits
1 circuit
1 circuit
Voltage circuit For each phase: 0.1VA (110V AC), 0.2VA (220V AC) For each phase: 0.1VA (110V AC), 0.2VA (220V AC), 0.4VA (440V AC) For each phase: 0.1VA (110V AC), 0.2VA (220V AC), 0.4VA (440V AC)
Current circuit
Consumption VA
For each phase: 0.1VA (current sensor primary side)
110V AC:2.0VA AC220V:3.0VA
Auxiliary power circuit (*10)
Measurement items
Current, demanded current, voltage, power, demanded power, reactive power, power factor, frequency, electric energy
ー
(regenerative, consumption), reactive electric energy(*7), current imbalance rate, voltage imbalance rate, operating time
Apparent power, periodic electric energy, harmonic current, harmonic voltage, Leakage current, demanded leakage current, resistance leakage current(*8),
demanded resistance leakage current(*8),
ー
pulse count value, pulse conversion value, electric energy conversion value
resistance leakage current difference conversion value(*8)
Main unit tolerances (*5)
Low sensitivity mode
Current, voltage, power, reactive power, apparent power, Current, voltage, power, reactive power, apparent power,
frequency: ±1.0% (relative to rated input)
Leakage current Io, resistive leakage current Ior: ±2.5%
frequency: ±1.0% (relative to rated input)
Power factor: ±3.0%
(relative to 10 to 100% of rating)
Power factor: ±3.0%
Electric energy: ±2.0%(in 5 to 100%
Leakage current Io, resistive leakage current Ior: ±2.5 mA
Electric energy: ±2.0%(in 5 to 100%
range of rated values; power factor = 1)
(relative to 10% of rating or lower)
range of rated values; power factor = 1)
Reactive electric energy: ±2.5% (in 10 to 100%
Reactive electric energy: ±2.5%
High sensitivity mode
range of rated values; power factor = 0)
(in 10 to 100% range of rated values; power factor = 0)
Leakage current Io, resistive leakage current Ior: ±2.5 mA
Harmonic current, harmonic voltage: ±2.5%
Names of Parts and
External view
External
input
specification
Simplified Comparison of
EcoMonitor Prod
Connection
Configurations
External view
External
output
specification
9
Data update cycle
Input signal format
Function
Contact input
Pulse input
Rated input voltage/current
Output signal format
Function
ー
ー
Leakage current: 2 sec, resistive leakage current: 2 sec
100msec
Non-voltage a contact, 1 input (Select function from below)
ー
ー
Contact/pulse input
ー
Monitoring of contact and measurement of
electric energy during operation (when contact is ON)
ー
ー
Counting of input pulse (count: 0 to 999,999)
ー
ー
ー
ー
Alarm output
ー
Plus output
ー
5V DC, 7 mA
ー
Non-voltage a contact, 1 output (Select function from below)
Alarm/pulse output
Alarm
Pulse output of electric energy
Select pulse unit from below.
0.001/0.01/0.1/1/10/100/1000/10000/100000(kWh/pulse)*6
ー
Contact output of alarm generating status
Contact output of alarm generating status
Select monitoring target from below.
Select monitoring target from below
Monitoring of current demand upper limit,
Leakage current first stage alarm
monitoring of current demand lower limit
Leakage current second stage alarm
Monitoring of N-phase current demand upper limit
Resistance leakage current first stage alarm
Monitoring of line voltage upper limit
Resistance leakage current second stage alarm
Monitoring of line voltage lower limit
Limit alarm of number of first stage alarm
Monitoring of phase voltage upper limit
occurrences of leakage current
Monitoring of phase voltage lower limit
Monitoring of power demand upper limit,
Limit alarm of number of second stage alarm
monitoring of power demand lower limit
occurrences of leakage current
Monitoring of power factor upper limit,
Limit alarm of number of first stage alarm
monitoring of power factor lower limit
occurrences of resistance leakage current
Monitoring of pulse conversion value upper limit
Monitoring of current imbalance rate upper limit Limit alarm of number of second stage alarm
occurrences of resistance leakage current
Monitoring of voltage imbalance rate upper limit
Rated switching voltage/current
35V DC 75 mA, 24V AC 75 mA (Power factor = 1)
ー
・Setting values
Power
Setting values, electric energy (consumption, regenerative), reactive electric energy,
・Number of alarm occurrences
Recorded item
interruption
periodic electric energy, operating time, pulse count value, pulse conversion value, electric energy
・Maximum value
backup
conversion value, maximum value, minimum value (Stored in the nonvolatile memory)
(Stored in the nonuvolatile memory)
Compatible standard
EMC: EN-61326-1:2013, Safety: EN-61010-1:2010
Operating temperature range
-5℃to +55℃ (ave. daily temp. of 35℃ or lower)
Operating
Operating humidity range
30% to 85%RH (no condensation)
environment Storage temperature range
-10℃ to +60℃ (ave. daily temp. of 35℃ or lower)
Altitude
2,000 m or lower
Between all terminals (excluding communication circuit and frame GND terminal) and external casing: 2,000V AC for 1 min
Commercial-frequency
Between all current/voltage inputs and all auxiliary power terminals: 2,000V AC for 1 min
withstand voltage
Between all current/voltage inputs, auxiliary power terminals and all contact/pulse inputs,
pulse/alarm outputs, communication terminals: 2,000V AC for 1 min
Insulation resistance
At the same locations as above: 10 MΩ or more (500V DC)
Auxiliary power/
A WG26-14 (single wire/stranded wires)
voltage input terminal
(Single wire: φ0.41 to φ1.62 mm, Stranded wires: 0.13 to 2.0 mm2)
Single wire: AWG24-17, Stranded wires: AWG20-26 (*9)
Compatible
Current input
(Single wire: φ0.5 toφ1.2 mm, Stranded wires: 0.5 to 1.3 mm2)
wire
AWG26-16 (single wire/stranded wires)
Input/output terminal
ー
(Single wire: φ0.41 to φ1.29 mm, Stranded wires: 0.13 to 1.3 mm2)
0.2 kg
Weight
External dimensions (unit: mm)
37.5 (W) x 90 (H) x 94 (D) mm (excluding protruding parts)
* 1 110V and 220V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 11,000V, and secondary voltage can be set
between 1 and 220V). For details, see the instruction manual.
* 2 110V, 220V and 440V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 6,600V, and secondary voltage can be set
between 1 and 220V). For details, see the instruction manual.
* 3 63.5V/110V – 277V/480V can be connected directly. An externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 6,600V, and secondary voltage can
be set between 1 and 220V). For details, see the instruction manual.
* 4 T he settable primary current when using the 5A current sensor is as follows:
6A、
7.5A、
8A、
10A、
12A、
15A、
20A、
25A、
30A、
40A、
50A、
60A、
75A、
80A、
100A、
120A、
150A、
200A、
250A、
300A、
400A、
500A、
600A、
750A、
800A、
1000A、
1200A、
1500A、
1600A、
2000A、
2500A、
3000A、
4000A、
5000A、
6000A、
5A、
8000A、
10000A、
12000A、
20000A、
25000A、
30000A(CT primary side can be set freely up to 30,000A. However, CT secondary side is fixed at 5A.)
7500A、
* 5 Refer to the specifications of options (split-type current sensor, 5A current sensor) on page 13 for the current sensor error rates.
* 6 Refer to the instruction manual for the detail on the setting of pulse unit.
* 7 Measurements are conducted based on a setting other than 2-circuit measurement mode with single-phase 2-wire setting.
* 8 It measures only in the case of Single-phase 2-wire, Single-phase 3-wire, 3-phase 3-wire.
* 9 Recommended bar terminal: Nichihu TGV TC-1.25-11T.
*10 Connected with optional units, it increases AC110V:4.5VA, AC220V:5.0VA.
Connected with display units, it increases AC110V:1.5VA, AC220V:2.0VA.
*11 110V, 220V and 440V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (maximum:600V AC). For details, see the instruction manual.
*12 63.5V/110V – 277V/480V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (maximum:600V AC). For details, see the instruction manual.
Product Lineup
■Extension
Extension Unit
Specification
Item
Energy Measuring Extension Unit for Different voltage system
EMU4-VA2
Model
Energy Measuring Extension Unit for Same Voltage System
EMU4-A2
Single-phase 2-wire/single-phase 3-wire,
3-phase 3-wire/3-phase 4-wire common
Single-phase 2-wire/
(Same as the unit connected on the left side)
110V, 220V, 440V AC common (*2)
3-phase 3-wire
Voltage
110V AC (between wires 1 and 2, and wires 2 and 3), 220V AC (between wires 1 and 3)
Single-phase
3-wire
circuit
220V AC (between wires 1 and 2, and wires 2 and 3), 440V AC (between wires 1 and 3)
3-phase 4-wire
Minimum: 63.5V/110V AC, Max.: 277V/480V AC (*3)
Instrument
50A, 100A, 250A, 400A, 600A
ratings
(Dedicated split-type current sensor is used. All values indicate primary current values of current sensor.)
Phase wire system
Current circuit
Features
5A
(Dedicated 5A current sensor is used. Current transformer (CT) is used in two-step configuration together with the
5A current sensor in order to allow a maximum primary current value setting of 30,000A) (*4)
Frequency
50/60Hz (automatic frequency selection)
(Same as basic unit)
Auxiliary power rating
2 circuits
No. of measurement circuits
2 circuits
Voltage circuit For each phase: 0.1VA (110V AC), 0.2VA (220V AC), 0.4VA (440V AC)
ー
Consumption VA
For each phase: 0.1VA (current sensor primary side)
Current circuit
AC110V:1.0VA AC220VA:1.5VA
Auxiliary power circuit
Measurement items
Current, demanded current, voltage, power, demanded power, reactive power, power factor, frequency, electric energy
(regenerative, consumption), reactive electric energy(*7), current imbalance rate, voltage imbalance rate, operating time
Apparent power, harmonic current, harmonic voltage, electric energy conversion value
External
input
specification
Pulse input
Rated input voltage/current
Output signal format
Function
Alarm output
ー
ー
ー
ー
ー
ー
ー
ー
ー
Non-voltage a contact, 1 output (Select function from below)
Alarm/pulse output
Contact output of alarm generating status
Select monitoring target from below.
Monitoring of current demand upper limit, monitoring of current demand lower limit
Monitoring of N-phase current demand upper limit
Monitoring of line voltage upper limit
Monitoring of line voltage lower limit
Monitoring of phase voltage upper limit
Monitoring of phase voltage lower limit
Monitoring of power demand upper limit, monitoring of power demand lower limit
Monitoring of power factor upper limit, monitoring of power factor lower limit
Monitoring of current imbalance rate upper limit
Monitoring of voltage imbalance rate upper limit
External view
Plus output
100msec
ー
Names of Parts and
External view
External
output
specification
Data update cycle
Input signal format
Function
Contact input
Specifications
Main unit tolerances (*5)
Current, voltage, power, reactive power, apparent power, frequency: ±1.0% (relative to rated input)
Power factor: ±3.0%
Electric energy: ±2.0%(in 5 to 100% range of rated values; power factor = 1)
Reactive electric energy: ±2.5% (in 10 to 100% range of rated values; power factor = 0)
Harmonic current, harmonic voltage: ±2.5%
Pulse output of electric energy
Select pulse unit from below.
0.001/0.01/0.1/1/10/100/1000/10000/100000(kWh/pulse)*6
Rated switching voltage/current
35V DC 75 mA, 24V AC 75 mA (Power factor = 1)
Setting values, electric energy (consumption, regenerative), reactive electric energy,
Recorded item
periodic electric energy, operating time, pulse count value, pulse conversion value, electric energy
conversion value, maximum value, minimum value (Stored in the nonvolatile memory)
Compatible standard
EMC: EN-61326-1:2013, Safety: EN-61010-1:2010
Operating temperature range
-5℃to +55℃ (ave. daily temp. of 35℃ or lower)
Operating
Operating humidity range
30% to 85%RH (no condensation)
environment Storage temperature range
-10℃ to +60℃ (ave. daily temp. of 35℃ or lower)
Altitude
2,000 m or lower
Between all terminals (excluding communication circuit and frame GND terminal) and external casing: 2,000V AC for 1 min
Commercial-frequency
Between all current/voltage inputs and all auxiliary power terminals: 2,000V AC for 1 min
withstand voltage
Between all current/voltage inputs, auxiliary power terminals and all contact/pulse inputs,
pulse/alarm outputs, communication terminals: 2,000V AC for 1 min
Insulation resistance
At the same locations as above: 10 MΩ or more (500V DC)
A WG26-14 (single wire/stranded wires)
Voltage input terminal
ー
(Single wire: φ0.41 to φ1.62 mm, Stranded wires: 0.13 to 2.0 mm2)
Single wire: AWG24-17, Stranded wires: AWG20-26 (*9)
Compatible
Current input
(Single wire: φ0.5 toφ1.2 mm, Stranded wires: 0.5 to 1.3 mm2)
wire
AWG26-16 (single wire/stranded wires)
Input/output terminal
(Single wire: φ0.41 to φ1.29 mm, Stranded wires: 0.13 to 1.3 mm2)
0.2kg
Weight
37.5 (W) x 90 (H) x 94 (D) mm (excluding protruding parts)
External dimensions (unit: mm)
Power
interruption
backup
Connection
Configurations
Simplified Comparison of
EcoMonitor Prod
* 1 110V and 220V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 11,000V, and secondary voltage can be set
between 1 and 220V). For details, see the instruction manual.
* 2 110V, 220V and 440V can be connected directly. Externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 6,600V, and secondary voltage can be set
between 1 and 220V). For details, see the instruction manual.
* 3 63.5V/110V – 277V/480V can be connected directly. An externally mounted voltage transformer (VT) for instrument is needed for voltages greater than those (primary voltage can be set to up to 6,600V, and secondary voltage can
be set between 1 and 220V). For details, see the instruction manual.
* 4 The settable primary current when using the 5A current sensor is as follows:
6A、
7.5A、
8A、
10A、
12A、
15A、
20A、
25A、
30A、
40A、
50A、
60A、
75A、
80A、
100A、
120A、
150A、
200A、
250A、
300A、
400A、
500A、
600A、
750A、
800A、
1000A、
1200A、
1500A、
1600A、
2000A、
2500A、
3000A、
4000A、
5000A、
6000A、
5A、
8000A、
10000A、
12000A、
20000A、
25000A、
30000A(CT primary side can be set freely up to 30,000A. However, CT secondary side is fixed at 5A.)
7500A、
* 5 Refer to the specifications of options (split-type current sensor, 5A current sensor) on page 13 for the current sensor error rates.
* 6 Refer to the instruction manual for the detail on the setting of pulse unit.
* 7 Measurements are conducted based on a setting other than 2-circuit measurement mode with single-phase 2-wire setting.
* 8 It measures only in the case of Single-phase 2-wire, Single-phase 3-wire, 3-phase 3-wire.
* 9 Recommended bar terminal: Nichihu TGV TC-1.25-11T.
10
3. Specifications
Specifications of MODBUS®RTU Communication
Product Lineup
Item
Physical interface
Communication protocol
Transmission method
Transmission wiring type
Baud rate
Data bit
Stop bit
Parity bit
Slave address
Features
Response time
Terminating resistor
Transmission distance
Maximum connectable devices
Recommended cable
Specification
RS-485 2wires half duplex
MODBUS® RTU mode
Asynchronous
Multi-drop bus (either directly on the trunk cable, forming a daisy-chain)
2400、4800、9600、19200、38400bps
(default: 19,200 bps)
8
1,2
(default: 1)
(default:EVEN)
ODD、EVEN、NONE
1∼255
(FFh)
(default: 1)
0: Broadcast
1s or shorter from completion of receiving query data to response transmission
120Ω 1/2W
1,200m
31 devices
SPEV
(SB)-MPC-0.2×3P (Mitsubishi cable industries)
Names of Parts and
External view
Specifications
■Compact display Unit
Item
Model
Supply power voltage
Auxiliary power
Consumption VA
Display device
Display refresh interval
Wh+A+4 element
Measurement
value display
Harmonic detail
Alarm status display
Alarm display
Alarm value display
EMU setting
Clock setting
Setting
Alarm setting
Display setting
Data reset
Data preset
Connection to energy measuring unit
Max. number of connectable units
Installation method
Operating temperature range
Operating humidity range
Storage temperature range
Weight
Specification
EMU4-D65
9V DC (Note 1)
ー
ー
LCD (with backlight)
1000 ms
Display of four elements: Electric energy, current and four other elements (selectable)
Display of detailed harmonic order data of harmonic current and harmonic voltage (Note 2)
Display of upper-/lower-limit alarm generating status and contact output status
Display of upper-/lower-limit alarm values and generating time
Setting of EcoMonitorPlus/EcoMonitorPro (phase wire, primary voltage, primary current, sensor type, demand time limit, pulse unit, measuring mode, etc.)
Setting of internal clock of EMU4-LM
Setting of upper-limit alarm value and lower-limit alarm value
Setting of LCD (with backlight) contrast and backlight ON status
Resetting of maximum value, minimum value, upper-/lower-limit alarm values, electric energy, reactive electric energy
Presetting of electric energy (consumption), reactive electric energy, electric energy conversion value, operating time,
electric energy (regenerative), pulse count value, pulse conversion value
Dedicated cable (supplied with product) used for connection. Cable extension: 10 m max. (Note 3)
7 units
Installs to IEC rail or panel
-5℃ to +55℃ (ave. daily temp. of +35℃ or lower)
30% to 80%RH (no condensation)
-10℃ to +60℃ (ave. daily temp. of +35℃ or lower)
0.1 kg
External view
*1 Supplied from energy measuring unit. However, when two or more units are connected, use commercial power supply units (compatible product: Cosel PBA15F-9-N1).
*2 Maximum value, minimal value and upper-/lower-limit alarm data are not displayed.
*3 When two or more units are connected, use the display unit connection cable (option). When extending the cable length, use the extension cable (option).
■Logging Unit
Basic Specification
Item
Model
Auxiliary power rating
Power interruption backup
Connection
Configurations
Set value
Logging data
System log data
Timer operation
Clock accuracy
Output data storage media*1
Simplified Comparison of
EcoMonitor Prod
Compatible model
11
Compatible standard
Operating temperature range
Operating
Operating humidity range
environment Storage temperature range
Altitude
Weight
External dimensions (unit: mm)
Parts sold separately
Consumables sold separately
Specification
EMU4-LM
6.4V DC (supplied from energy measuring unit)
Total power interruption backup time of the battery (EMU4-BT) is one year (ave. daily temp. of 35℃ or lower). It is recommended to replace the battery every three years.
Saved in nonvolatile memory
* Data will not be lost even if power outage occurs.
Saved in volatile memory
* Data will be lost if power outage occurs when the battery voltage is low (BAT.LED is lit).
Timer operation continues by using the battery in the event of power outage.
* Timer operation stops if the battery voltage is low (BAT.LED is lit) when power outage occurs.
After power is recovered, timer operation starts from 2013/01/01 00:00:00.
1 min/month
SD memory card (SD, SDHC)
Energy measuring unit (EcoMonitorLight)
Model: EMU4-BD1-MB, EMU4-HD1-MB
Energy measuring unit (EcoMonitorPlus)
Model: EMU4-BM1-MB, EMU4-HM1-MB, EMU4-LG1-MB, EMU4-VA2, EMU4-A2
EMC: EN-61326-1:2006
-5℃ to +55℃ (ave. daily temp. of +35℃ or lower)
30% to 85%RH (no condensation)
-10℃ to +60℃ (ave. daily temp. of +35℃ or lower)
2,000m or lower
0.1 kg *Wight of logging unit only
25 (W) x 99 (H) x 60 (D) mm *Dimensions of logging unit only
SD memory card (EMU4-SD2GB)*1*2
Battery (EMU4-BT)*2
*1 Use Mitsubishi SD memory card (EMU4-SD2GB).
If an SD memory card other than above is used, data in the SD memory card may become damaged or problems such as a system shutdown may
occur. Regarding the use of commercially available SD memory cards, access our FA website. Note that the customer is responsible for verifying safe
use of those SD memory cards.
*2 To purchase parts and consumables that are sold separately, contact the dealer from which the product was purchased.
Logging Specifications
Specification
Item
Automatic update
Automatic overwrite/update
Date/time designation Automatic start/stop according to start time setting
Measurement data is saved according to set "Detailed Data Logging Cycle"
Detailed data
(1 sec, 1 min, 5 min, 10 min, 15 min, 30 min).* Output as a detailed data file
Logging data type
Measurement data is saved in 1-hour cycles.
1-Hour data
* Output as 1-hour and 1-day data files.
Detailed data logging cycle of 1 sec → Maximum of 4 elements
Detailed data
Number of
Detailed data logging cycle of other than 1 sec → Maximum of 10 elements
logging elements
Maximum of 10 elements
1-Hour data
Number of connected extension units None
1 unit
2 units
Detailed data logging cycle: 1 sec 20 hours
6 hours
3 hours
Detailed data logging cycle: 1 min 20 days
6 days
3 days
Detailed data
Detailed data logging cycle: 5 min 100 days
30 days
15 days
Internal memory
Detailed data logging cycle: 10 min 200 days
60 days
30 days
logging period
90 days
45 days
Detailed data logging cycle: 15 min 300 days
Detailed data logging cycle: 30 min 600 days
180 days
90 days
Number of connected extension units None
1unit
2unit
1-Hour data
−
620 days (approx.20 months) 186 days (approx. 6 months) 93 days (approx. 3 months)
1unit
2unit
Number of connected extension units None
SD memory card (2GB)
Detailed data logging cycle of 1sec 341 days (approx.11 months) 186 days (approx. 6 months) 93 days (approx. 3 months)
Logging period*1
142 months
93 months
Detailed data logging cycle of 1min 370 months
Detailed data logging cycle of 5min,10 min,15 min,30 min → 10 years or more
System log data
3,600 records
Logging data and system log data output format CSV format (ASCII code)
Product Lineup
Logging mode
Features
3 units
2 hours
2 days
10 days
20 days
30 days
60 days
3unit
62 days (approx. 2 months)
3unit
62 days (approx. 2 months)
64 months
*1 The indicated period is the time period during which data can be saved in a 2GB SD memory card without exceeding its capacity.
The amount of data varies depending on the number of characters. The logging period indicates output at maximum capacity.
Specifications
■CC-Link Communication Unit
Basic Specifications
Item
Model
Rating
Names of Parts and
External view
Specification
EMU4-CM-C
6.4V DC (supplied from energy measuring unit)
Energy measuring unit (EcoMonitorLight)
Model: EMU4-BD1-MB, EMU4-HD1-MB
Compatible model
Energy measuring unit (EcoMonitorPlus)
Model: EMU4-BM1-MB, EMU4-HM1-MB, EMU4-LG1-MB, EMU4-VA2, EMU4-A2
Compatible standard
EMC: EN-61326-1:2006
Operating temperature range -5℃ to +55℃ (ave. daily temp. of +35℃or lower)
Operating
Operating humidity range 30% to 85%RH (no condensation)
environment
Storage temperature range -10℃ to +60℃(ave. daily temp. of +35℃or lower)
Altitude
2,000m or lower
Weight
0.1 kg *Wight of CC-Link communication unit only
25(W)×99(H)×60(D)
External dimensions (unit: mm)
CC-Link Communication Specifications
Item
Number of Occupied Station
CC-Link Ver.1.10 Ver.2.00
(Set by Version charge switch)
Remote Station Number (Station Number)
Max.connected device
Cable terminating resistance
Ver.1.10, Ver 2.00(Set by version charge switch)
1 to 64
156k, 625k, 2.5M, and 10Mbps (changes according to setting)
(The interstation cable length and maximum total extension distance vary according to the transmission speed.)
A maximum of 42 units can be connected if configured using only this module.
Use a specified cable for CC-Link communication connection.
Resistance values for terminating resistance are different according to the type of specialized cable used.
■Optional Parts
Split-type Current Sensor
Item
Item
Model
Rated primary current
Rated secondary current
Rated load
Maximum use voltage
Ratio error
Phase difference variation
Measurement category
Degree of contamination
Operating temperature range
Operating humidity range
CE marking compatible standard
Maximum voltage compatible with CE marking
Weight (1 unit)
EMU-CT100
100A AC
33.33mA
0.1VA
460V AC
±1% (5 to 100% of rating, RL ≤ 10 Ω)
±30 min. (5 to 100% of rating, RL ≤ 10 Ω)
III
2
-5 C to +55 °C (daily average temperature of 35°C or less)
5% to 95% RH (no condensation)
EN61010-2-32
460V AC
0.1kg
Specifications
EMU2-CT5、EMU2-CT5-4W
5A AC
1.66mA
0.1VA
260V AC
±1%(5 to 100% of rating)
±30 min. (5 to 100% of rating, RL ≤ 10 Ω)
III
2
-5 C∼+55 C (daily average temperature of 35 C or less)
5%∼95%RH (no condensation)
EN61010-2-32
260V AC
0.1kg
EMU-CT250
250A AC
66.66mA
0.7kg
Simplified Comparison of
EcoMonitor Prod
5A Current Sensor
Specifications
EMU-CT50
50A AC
16.66mA
Connection
Configurations
Model
Rated primary current
Rated secondary current
Rated load
Maximum use voltage
Ratio error
Phase difference variation
Measurement category
Degree of contamination
Operating temperature range
Operating humidity range
CE marking compatible standard
Maximum voltage compatible with CE marking
Weight (1 unit)
External view
Baud Rate
Specification
1 Station Remote device station (I/o)data and word data can be transmitted
12
3. Specifications
■Optional Parts
Product Lineup
Split-type Current Sensor
Features
Item
Model
Rated primary current
Rated secondary current
Maximum operating voltage
Measurement category
Degree of contamination
Operating temperature range
Operating humidity range
CE marking compatible standard
Maximum voltage compatible with CE marking
Weight (1 unit)
EMU-CT50-A
50A AC
16.66mA
Specification
EMU-CT250-A
EMU-CT400-A
250A AC
400A AC
66.66mA
66.66mA
460V AC(*1*2)
EMU-CT100-A
100A AC
33.33mA
ー
ー
0.1kg
0.1kg
EMU-CT600-A
600A AC
66.66mA
EMU-CT5-A
5A AC
1.66mA
Ⅲ
2
-10∼+55℃ (ave. daily temp. of 35℃ or lower)
25% to 95%RH (no condensation)
EN61010-2-32
460V
0.2kg
0.3kg
0.4kg
ー
ー
ー
ー
ー
ー
0.1kg
*1 Current sensor does not support a non-insulation electric wire or a metal for a primary cable.
*2 Maximum operating voltage indicates voltage to ground.
SD Memory Card
Lithium Battery for Logging Unit
Specifications
Item
Model
Memory capacity
Weight
Item
Model
Type
Nominal voltage
Capacity
Weight
Specification
EMU4-SD2GB
2GB
2g
Specification
EMU4-BT
Manganese dioxide lithium battery
3V
220mAh
3g
* One battery supplied with logging unit.
External view
Names of Parts and
External view
Split-type Zero-phase Current Transformer
Item
Model
Hole diameter (mm)
Allowable current (A)
Weight (kg)
Rated short-time current
CZ-22S
22
50
0.5
CZ-30S
30
100
0.6
Through-type Zero-phase Current Transformer
Specification
CZ-55S
55
300
1.8
50 kA (peak-to-peak value: 100 kA)
CZ-77S
77
600
2.8
CZ-112S
112
1.000
2.8
Zero-phase Current Transformer with Primary Conductor
Item
Model
Hole diameter (mm)
Specification
Item
ZT100B
ZT80B
ZT60B
ZT30B
ZT40B
ZT15B
Model
Allowable current (A)
100
80
60
40
15
30
Weight (kg)
Refer to the following table, "Zero-phase Current transformer (ZCT) inside Diameter,
Allowable current
Maximum Through-wire Diameter and Allowable Current."
Rated burden
Number of polarities
Weight (kg)
3.3
2.6
2.0
0.2
0.4
0.6
Rated short-time current
Rated short-time current
50 kA (peak-to-peak value: 100 kA)
Specification
ZTA1200A
ZTA2000A
1200
2000
11
27
3
AC600V
100 kA (peak value)
ZTA600A
600
6.5
Zero-phase Current transformer (ZCT) inside Diameter, Maximum Through-wire Diameter and Allowable Current
Wiring
Simplified Comparison of
EcoMonitor Prod
Connection
Configurations
of
Phase wire No.
wires
13
Maximum through-wire diameter (mm2)
(Allowable current (A) of wire)
Split type
Wire type
CZ-22S CZ-30S CZ-55S CZ-77S CZ-112S ZT15B
600V
22
60
250
500
14
polyvinyl-insulated wire
ー
(115) (217) (556) (842)
(88)
(IV)
Single-phase 2-wire
2
600V cross-linked
22
38
200
500
2
1000
polyethylene-insulated wire
Single-core wire (CV wire) (130) (190) (545) (920) (1465) (33)
600V
22
38
200
500
8
polyvinyl-insulated wire
ー
(115) (162) (496) (842)
(61)
(IV)
Single-phase 3-wire
3
600V cross-linked
3-phase 3-wire
2
800
14
22
150
325
polyethylene-insulated wire
Single-core wire (CV wire) (100) (135) (455) (760) (1285) (33)
*1 Note that the wire thickness may vary slightly depending on the manufacturer.
*2 The IV wire applies to cases where insulators are used.
*3 The IV wire applies to cases where insulation in a covered conduit in air.
(Cables of 600mm2 or more have various structures. The values are shown for reference. )
Through type
ZT30B
ZT40B
ZT60B
ZT80B
ZT100B
60
150
325
600
800
(217) (395) (650) (992) (1185)
38
60
250
400
600
(190) (260) (655) (870) (1140)
38
100
250
500
725
(162) (298) (556) (842) (1095)
22
60
200
325
600
(135) (260) (560) (760) (1140)
■Software
Item
Specification
・Microsoft Windows 8.1 Pro(32bit,64bit)
・Microsoft Windows 7 Professional (32bit,64bit) SP1
・Microsoft Windows Vista Ultimate 32bit SP2
OS
Recommended
system
environment
Microsoft .NET Framework
Microsoft Excel
Max. number of connectable units
Language
Data
collection
function
Periodic collection
Current value display
Max. number of collection points
Communication setting
Terminal setting
Measurement item registration
Report output
・Microsoft Excel 2003 SP3
・Microsoft Excel 2007 SP3
・Microsoft Excel 2010 SP1
・Microsoft Excel 2013 SP1
31 units
Japanese, English
Data is collected in 1-min or 1-hr cycles.
(Operated in background only when application is booting)
Constant communication is performed to display current values.
124 points
MODBUS ® RTU communication setting (baud rate, stop bit length, etc.)
Registration of terminals used for data collection
Specifications
Terminal registration
・Microsoft .NET Framework 2.0
・Microsoft .NET Framework 3.5
・Microsoft .NET Framework 3.5.1
Features
Basic
specification
Setting
function
Product Lineup
Data Acquisition Software (EMU4-SW1)
Function to write/read settings (such as phase wire, rated current and rated voltage) to/from terminals
Registration of measurement items to be collected
Export/import
Communication, terminal and measurement item settings can be saved to or read from file.
Output format
Output type
Monthly report, daily report, details (1-min intervals)
Pasting of aggregate data in master file (Excel file) (Master files can be added or changed freely.)
* Data acquisition software carries out free download, and gets from the “design supportive tool data” of the Mitsubishi Electric web site energy saving supportive equipment menu.
Item
Specification
・Microsoft Windows 7 Professional SP1
(32bit/64bit)
・Microsoft Windows 8.1 Pro Update
(32bit/64bit)
OS
NET Framework
Microsoft Excel
System
requirements
・Microsoft Excel 2010 SP2(32bit)
・Microsoft Excel 2013 SP1 (32bit)
CPU
Conformity with OS system requirements
RAM
Conformity with OS system requirements
Hard disk
Input device
External interface
Supported languages
Output format
Max. number of sheets
Document type
Monthly report
Weekly report
Daily report
Details (min)
Details (sec)
XGA or higher resolution display monitor
(65,536 colors, 1024 x 768 pixels or more)
Mouse and keyboard
SD memory card slot or SD memory card reader/writer
Japanese, English
Logging data pasted to template Excel file
(template Excel file is freely editable)
Logging data can be pasted to maximum of 31 sheets
(for data of 31 logging units)
Output of 1-day interval data of a period of 1 month
Output of 1-hour interval data of a period of 7 days
Output of 1-hour interval data of a period of 1 day
Output of 30-/15-/10-/5-/1-minute interval data of specified period (1 to 24 hours)
Output of 1-sec interval data of a period of 1 hour
Creation/editing of logging setting data file (set.csv)
* Documentation software carries out free download, and gets from the “design supportive tool data” of the Mitsubishi Electric web site energy saving supportive equipment menu.
Connection
Configurations
Report
creation
Software requires approximately 20 MB of free space to install
(additional space is required for saving document files created by the software).
External view
Display
Logging setting
・Microsoft .NET Framework 4 Client Profile
Names of Parts and
External view
Logging Unit Utility
Simplified Comparison of
EcoMonitor Prod
14
4. Names of Parts and External View
Product Lineup
[Energy Measuring High Performance Model]EMU4-HM1-MB
Frame GND Terminal
Connect to ground. (D type ground)
4
37.4
Auxiliary Power Terminal
Connect the auxiliary power supply.
Features
4.5
Voltage Input Terminal
Connect the voltage input wire
from the measuring circuit.
MODEL
EMU4-HM1-MB
Connector (compact display unit)
Connect the connector of
the compact display unit.
90
Specifications
LED
Displays the operating
status of the unit.
Reset Button
Press to reset the unit.
4.5
MODBUS® Communication Terminal
Connect the MODBUS
communication cable.
External view
External Input Terminal
Connect the pulse/
contact output line.
[Energy Measuring Standard Model] EMU4-HM1-MB
4
37.5
1.1
[Insulation Monitor Model] EMU4-LG1-MB
92.9
4
4.5
EMU4-BM1-MB
35.4
MODEL
EMU4-LG1-MB
74.4
* This side view also applies to other basic unit models (EMU4-BM1-MB, EMU4-HM1-MB, EMU4-LG1-MB).
4.5
27
4.5
Simplified Comparison of
EcoMonitor Prod
15
37.5
4.5
MODEL
90
Connection
Configurations
90.6
90
Names of Parts and
External view
Current Input Terminal
Connect the secondary output
of the dedicated current
sensor connected to the
current wire of the
measurement circuit.
92.9
37.5
59.8
EMU4-VA2
EMU4-A2
90
6.6
[CC-Link Communication Unit] EMU4-CM-C
60
25
15
6.6
60
4
4.5
4.5
4
74.4
Specifications
25
27
4.5
4.5
74.4
[Logging Unit] EMU4-LM
15
L RUN
4
2
1
8
4
2
1
L ERR
RD
156 K
625 K
2.5M
5M
10 M
RESET
27
27
BATTERY
4
17.6
VER.
B RATE
35.4
→ON
90
4
35.4
17.6
90
SD
STATION NO.
SD CARD
BAT.
Names of Parts and
External view
LOG.
SD C.
Features
27
90
35.4
MODEL
35.4
MODEL
4
92.9
90.6
4.5
37.5
4.5
4
[Energy Measuring Extension Unit for Same Voltage System]
EMU4-A2
Product Lineup
[Energy Measuring Extension Unit for Different Voltage System]
EMU4-VA2
10.2
4.5
4.5
External view
35.2
Connection
Configurations
Simplified Comparison of
EcoMonitor Prod
16
5. External View
Product Lineup
[Compact Display Unit] EMU4-D65
65
LCD display device:
Displays the values measured by energy
measuring unit and setting information.
Circuit display:
Lit circuit no. indicates the circuit displayed
on the screen. When alarm is generated,
the LED of the pertinent circuit no. flashes.
SETUP key:
Used to activate the setting mode
and exit from it.
65
Master LED:
Lights when operating as a master unit.
It does not light when operating
as a slave unit.
REST/SET key:
Used to reset/preset data.
Features
▲、▼keys
Used to change measurement data
or select menu item.
CIRCUIT key:
Changes and displays
measurement circuits.
/PHASE key:
Changes and displays the phase
data of current/voltage.
Also used to enter settings.
[Split-type Current Sensor] EMU-CT100-A
31.6
43.6
14
12.8
19
33.6
16.2
65
57.5
5
16.2
12.2
37.4
External view
Names of Parts and
External view
[Split-type Current Sensor] EMU-CT5-A, EMU-CT50-A
5
Specifications
+ - keys:
Displays/hides maximum values
and minimum values and switches
harmonic order data.
[Split-type Current Sensor] EMU-CT250-A
Connection
Configurations
42.6
49.4
44.9
67.2
24
27
36
17
94
4.5
74.5
Simplified Comparison of
EcoMonitor Prod
4.5
36
24
25.2
[Split-type Current Sensor] EMU-CT400-A, EMU-CT600-A
[Split-type Current Sensor]
Product Lineup
Split-type Current Sensor EMU-CT50、EMU-CT100、EMU-CT250
A
B
Terminal protection cover
Secondary terminal screw
C
L
D
E
K
Movable core
fixing tab
Model
Features
Stopper
Movable core
F
A
B
C
D
E
F
EMU-CT50/CT100
31.5
39.6
55.2
25.7
15.2
18.8
EMU-CT250
36.5
44.8
66.0
32.5
22.0
24.0
5A Split-type Current Sensor
(300)
30
(200)
Detail of Sensor Part
Specifications
1Side
500
3Side
(200)
500
(300)
12
1
1Side
44
5A Split-type Current Sensor
Names of Parts and
External view
11
1
37
3Side
2Side
External view
[Current Sensor Cable]
5A Split-type Current Sensor Cable EMU2-CB-Q5A
5A Split-type Current Sensor Extension Cable (Standard Type) EMU2-CB-T**M
1k
1l
3k
3l
EMU2-CB-T1M
1m
EMU2-CB-T5M EMU2-CB-T10M
5m
10m
5A Split-type Current Sensor Extension Cable (separate Type) EMU2-CB-T**MS
500
1k
1l
3k
3l
2k
2l
Model
L dimension
EMU2-CB-T1MS EMU2-CB-T5MS EMU2-CB-T10MS
1m
5m
10m
Simplified Comparison of
EcoMonitor Prod
5A Split-type Current Sensor EMU2-CB-Q5A-4W
Model
L dimension
Connection
Configurations
500
18
5. External View
[Zero-phase Current Transformer]
Product Lineup
ZT15B・30B・40B
ZT60B・80B・100B
Mounting hole
(Mounting screw M6×20)
Terminal screw M3.5
Mounting hole
(Mounting screw
M5×0.8×20)
CZ-22S・30S・55S・77S・112S
Terminal screw M3.5
Features
CZ-22S/30S/55S/77S
■ZT15B/30B/40B Dimensional variation table
Specifications
A
B
C
D
E
F
G
H
■ZT60B/80B/100B Dimensional variation table
ZT15B
ZT30B
ZT40B
48
15
29
62
46
15
70
25
68
30
37
82
66
30
90
50
85
40
43
92
81
40
100
50
A
B
C
D
E
ZT60B
ZT80B
ZT100B
140
60
73
150
46
160
80
82
169
48
185
100
93
190
50
CZ-112S
■ZT15B/30B/40B Dimensional variation table
External view
Names of Parts and
External view
A
B
C
D
E
F
G
H
J
K
CZ-22S CZ-30S CZ-55S CZ-77S CZ-112S
55
22
30
77
112
32
27
27
41
57
148
100
114
198
234
160
112
130
210
246
177
128
144
232
268
5
5
8
8
10
30
30
36
62
45
12
12
12
12
12
41
47
66
109
90
77
89
124
207
171
ZTA600A(600A)
・ZTA1200A(1200A)
・ZTA2000A(2000A)
ZTA600A
(600A)
ZTA1200A
(1200A)
ZTA2000A
(2000A)
Simplified Comparison of
EcoMonitor Prod
Connection
Configurations
φ11
Bolt M10
19
φ9
Mounting
hole
φ11
Bolt M10
φ11
Mounting
hole
φ13
Mounting hole
φ13
Bolt M12
6.Connection Configuration
[Power Measurement]
Power supply side
1
2
0.5A fuse
L
l
MA
P3
P1
k
MB
NC
P2
EMU-CT***-A
Split-type current sensor
(50/100/250/400/600)
K
Product Lineup
Single-phase 2-wire (in the case of low-voltage circuit)
1K
Features
1L
2K
2L
3K
3L
485+
485-
Ter
SLD
Specifications
RS485(MODBUS®)
Load side
Name
EcoMonitorPlus (Standard Model)
Model
EMU4-BM1-MB
Quantity
1
EMU-CT***-A
(50/100/250/400/600)
Split-type current sensor
1
Power supply side
1 2
1 N
3
3
l
k
l
1L 3K
1Current transformer
(5A secondary current)
3L
K
L
k
l
K
k
L
l
K
k
L
l
K
k
l
3L
K
L
k
l
K
k
K
L
K
K
L
k
l
K
L
k
l
Circuit 5
0.5A fuse
L
K
k
l
k
1K
1L 2K
L
K
l
k
2L 3K
l
K
1K
1K
1K
1K
1L
1L
1L
1L
2K
2K
2K
2K
2L
2L
2L
2L
2L
3K
3K
3K
3K
3K
3L
3L
3L
3L
3L
485-
SLD
Ter
Y1
COMY1
Y2
COMY2
Y1
COMY1
1K
1L
Y2
l
K
L
k
l
k
2L 3K
l
3L
1K
1L
2K
2L
3K
3L
k
l
k
l
k
l
K
L
K
L
K
L
External
output 1 External output 1 External
output2
output2
k
K
l
L
k
K
l
L
k
K
Name
Model
EMU4-BM1-MB
EcoMonitorPlus (Extension Unit for Same Voltage System) EMU4-A2
EMU-CT***-A
Split-type current sensor
(50/100/250/400/600)
EcoMonitorPlus (Standard Model)
Quantity
1
2
10
L
1K
1K
1K
1L
1L
1L
2K
2K
2L
2L
2L
3K
3K
3K
3L
3L
3L
SLD
X1
Ter
Y1
Y1
COMY1
2K
Y2
COMY2
COMX1 COMY1
External
output 1
External output 2
External input 1
External output 1
RS485(MODBUS®)
Load side
Load side
l
485-
MA
P3/P3
COMY2
Circuit 1
k
l
1L 2K
MB
NC/P2
P1/P1
2K
RS485(MODBUS®) External
Circuit 1
l
L
Name
Model
EMU4-HM1-MB
EcoMonitorPlus (Extension Unit for Same Voltage System) EMU4-A2
EcoMonitorPlus (High Performance Model)
5A current sensor
EMU-CT5-A
Quantity
1
1
9
Simplified Comparison of
EcoMonitor Prod
1L 3K 3L
L
L K
Connection
Configurations
P2/P0
EMU-CT5-A
5A current sensor
485+
K
L K
MB
MA
P3
P1
k
L
l
3L
k
1K
K
L
1K
485+
L
l
0.5A fuse
1K 1L 3K 3L
NC
K
k
k
l
1K 1L 3K 3L
P2
L
l
k
Circuit 4
k
1K 1L 3K
L
Circuit 3
K
L
l
External view
L
Voltage transformer
for instrument
3 N
Circuit 3
1K
K
2
Circuit 2
L
k
1
Circuit 2
K
3-phase 4-wire (in the case of high-voltage circuit)
Power supply side
EMU-CT***-A形
分割形電流センサ
(50/100/250/400/600)
Names of Parts and
External view
Single-phase 3-wire/3-phase 3-wire (in the case of low-voltage circuit)
20
6.Connection Configuration
Product Lineup
Single-phase 3-wire/3-phase 3-wire (in the case of high-voltage circuit)
System1 System2
Power supply Power supply
side
side
1 2 3
1 N 3
3-phase 4-wire (in the case of low-voltage circuit)
System3
Power supply side
1 2 3
1 N 3
System1
System2
Power supply side
1 2 3 N
1 2 3
1 N 3
Voltage transformer
for instrument
Power supply side
1 2 3 N
0.5A fuse
0.5A fuse
MB
MA
P3
P1
P2/P0
NC
P3/P3
1K
1K
1K
1K
1L
1L
1L
1L
1L
2K
2K
2K
2L
2L
2L
2L
3K
3K
3K
3K
3L
3L
3L
SLD
Y1
Ter
COMY1
Y2
3L
Y1
COMY2
COMY1
P2/P0
2K
2L
3K
485-
1L 1K 3L 3K
3L
Y2
COMY2
1L 1K 3L 3K
k
l
k
l
K
L K
L
k l
K L
External
External
output 1 External output 1 External
output 1
output 1
k
K
l
l
K
L K
L
k
l k
l
K
L K
L
485-
5A current
sensor
EMU-CT5-A
K
K L
l k
L K
1K 1L 2K 2L 3K 3L
Circuit 3
Names of Parts and
External view
1K
1L
1L
2L
2L
3K
3K
3L
3L
3L
X1
Y1
Y1
COMY1
L
K
l
k
2K
3L
3K
2K
2L
3K
Ter
k
1K 2L
Y2
COMY2
3L
COMX1 COMY1
3K 2L
External
output 1
l k
L K
k
l
K
Lk
External input 1 External
output 1 External
output 1
RS485(MODBUS®)
l
L k
l
K
L
2K
1L 1K
l
k
l
k
L
K
l
k
L
K
L
K
EMU-CT***-A
Split-type current sensor
(50/100/250/400/600)
Load side
Load side Load side
Load side
Load side
Name
Model
EcoMonitorPlus (Standard Model)
EMU4-BM1-MB
EcoMonitorPlus
(Extension Unit for Different Voltage System) EMU4-VA2
5A current sensor
Quantity
Name
Model
1
EcoMonitorPlus (High Performance Model) EMU4-HM1-MB
EcoMonitorPlus
1
(Extension Unit for Different Voltage System) EMU4-VA2
EMU-CT***-A
Split-type current sensor
9
(50/100/250/400/600)
Quantity
1
2
EMU-CT5-A
10
[Electric Leakage Measurement]
Single-phase/3-phase 3-wire
3-phase 3-wire(with the voltage transformer)
3P3W(with the voltage transformer) * Do not use high-voltage circuit.
1P3W/3P3W
Power supply side
1
1
External view
1K
1L
SLD
K
l
NC
1K
2K
L
k
K
k l
K L
k
NC
NC
P3/P3
P1/P1
2K
l k
L K
Current transformer
(5A secondary current)
k l
K L
NC/P2
Circuit 1
k l
K L
1L 1K 3L 3K
Circuit 2
k l
K L
L
K
l
Circuit 3
l k
Circuit 5
k
k l
P2/P0
MA
P3/P3
l k
K
L
L
1L
1L 1K 3L 3K
1L 1K 3L 3K
Specifications
k l
K L
485+
Circuit 1
k l
K L
RS485(MODBUS®)
l
L
MB
NC/P2
P1/P1
Circuit 4
Features
P1/P1
NC
NC
NC/P2
1K
2K
485+
P2/P0
NC
P3/P3
P1/P1
NC
NC
NC/P2
Circuit 2
NC
P2
N
2
Zero-phase
current
transformer
(ZCT))
3
3
Power supply side
1
0.5A fuse
P2/P0
0.5A fuse
3
MB
NC/P2
Zero-phase
current transformer
(ZCT))
MA
P3/P3
P1/P1
2
P2/P0
MB
NC/P2
MA
P3/P3
P1/P1
Z+
Z+
Connection
Configurations
Z
NC
Z
NC
NC
NC
NC
NC
NC
NC
485+
SLD
NC
Y1
485+
485-
Ter
NC
Simplified Comparison of
EcoMonitor Prod
485-
21
External output
Load side
SLD
NC
Y1
COMY1
Ter
NC
COMY1
External
output
RS485(MODBUS®)
RS485(MODBUS®)
Load side
*Regarding the installation and connection of units, refer to the instruction manual.
7.Simplified Comparison of EcoMonitor Products
Product Lineup
EcoMonitorPlus
Obtain the most appropriate measurements according to applications!
[Features]
・Easy system expansion by adding units.
・Collection of data from multiple circuits (up to
14 circuits) and easy creation of reports.
・Monitoring of leakage currents and load
currents for equipment maintenance and
management.
Features
Specifications
Simple and easy measuring at low cost!
[Features]
・Reasonable price.
・Integrated setting display device.
・Easy installation and measuring operation.
Names of Parts and
External view
EcoMonitorPro
External view
Measure up to 7 circuits!
[Features]
Connection
Configurations
・Capable of measuring a wide range of voltage
from low to high.
・Single unit for measurement of different
voltage/phase wires.
・A wide lineup of models with momentary
voltage drop detection and pulse output
functions.
Simplified Comparison of
EcoMonitor Prod
22
Energy Measuring Unit
Country / Region
Australia
Company
Mitsubishi Electric Australia Pty. Ltd.
USA
Mitsubishi Electric Automation Inc.
Brazil
MELCO-TEC Rep. Com. e Assessoria Tecnica Ltda.
Agua Santa 4211 P.O. Box 30-D Vina del Mar, Chile
+56-32-2-320-600
No. 1386 Hongqiao Road, Mitsubishi Electric Automation Center
Shanghai China, 200336
+86-21-2322-3030
Proelectrico Representaciones S.A.
Carrera 53 No 29C-73 - Medellin, Colombia
+57-4-235-30-38
Cairo Electrical Group
9, Rostoum St. Garden City P.O. Box 165-11516
Maglis El-Shaab, Cairo - Egypt
+20-2-27961337
Rhona S.A.
Mitsubishi Electric Automation (CHINA) Ltd.
China
Mitsubishi Electric Automation (HongKong) Ltd.
Europe
Mitsubishi Electric Europe B.V.
India
Mitlite Electric Company Pvt Ltd
P. T. Sahabat Indonesia
Indonesia
+1-847-478-2100
+55-11-3146-2200
Chile
Egypt
500 Corporate Woods Parkway Vernon Hills, IL 60061, USA
Telephone
+61-2-9684-7777
Av. Paulista, 1439-Cj.72, Cerqueira Cesar CEP 01311-200,
Sao Paulo, SP, CEP:01311-200, Brazil
China
Colombia
Address
348 Victoria Road, Rydalmere, N.S.W. 2116, Australia
10/F., Manulife Tower, 169 Electric Road, North Point,
Hong Kong
+852-2887-8810
Mitsubishi-Electric-Platz1,40882 Ratingen,Germany
+49-2102-486-0
P.O.Box 5045 Kawasan Industri Pergudangan,
Jakarta, Indonesia
+62-(0)21-6610651-9
Plot No-32, Sector-6, IMT Maneser,
1480-6, Gayang-Dong, Gangseo-Gu, Seoul, Korea
+91-124-4695300
+82-2-3660-9572
Korea
Mitsubishi Electric Automation Korea Co., Ltd
Laos
Arounkit Corporation Import-Export Solt Co., Ltd. Saphanmo Village. Sayaetha District,Vientiane Capital,Laos
+856-20-415899
Comptoir d'Electricite Generale-Liban
+961-1-240445
Lebanon
Malaysia
Myanmar
Middle East
Arab Countries & Cyprus
Pakistan
Philippines
Saudi Arabia
Singapore
South Africa
Taiwan
Mittric Sdn Bhd
5 Jalan Pemberita U1/49, Temasya Industrial Park,
Glenmarie 40150 Shah Alam, Selangor, Malaysia
+603-5569-3748
Peace Myanmar Electric Co.,Ltd.
NO137/139 Botataung Pagoda Road,
Botataung Town Ship 11161, Yangon, Myanmar
+95-(0)1-202589
Watt & Volt House
Nepal
Cebaco Center - Block A Autostrade Dora,
P.O. Box 11-2597 Beirut - Lebanon
Comptoir d'Electricite
Generale-International-S.A.L.
Prince Electric Co.
Edison Electric Integrated, Inc.
Center of Electrical Goods
Mitsubishi Electric Asia Pte. Ltd.
CBI-electric: low voltage
Setsuyo Enterprise Co., Ltd
KHA 2-65, Volt House Dillibazar Post Box: 2108,
Kathmandu, Nepal
Cebaco Center - Block A Autostrade Dora
P.O. Box 11-1314 Beirut - Lebanon
1&16 Brandreth Road, Lahore-54000, Pakistan
24th Fl. Galleria Corporate Center, Edsa Cr. Ortigas Ave.,
Quezon City Metro Manila, Philippines
Al-Shuwayer St. Side way of Salahuddin Al-Ayoubi St.
P.O. Box 15955 Riyadh 11454 - Saudi Arabia
307, Alexandra Road, #05-01/02
Mitsubishi Electric Building, Singapore 159943
Private Bag 2016, Isando, 1600, South Africa
6th Fl., No.105, Wu Kung 3rd, Wu-Ku Hsiang,
Taipei, Taiwan, R.O.C.
+977-1-4411330
+961-1-240430
+92-(0)42-7654342
+63-(0)2-634-8691
+966-1-4770149
+65-6473-2308
+27-(0)11-9282000
+886-(0)2-2298-8889
77/12 Bamrungmuang Road, Klong Mahanak,
Pomprab Bangkok Thailand
+66-223-4220-3
Thailand
United Trading & Import Co., Ltd.
Uruguay
Fierro Vignoli S.A.
Avda. Uruguay 1274, Montevideo, Uruguay
+598-2-902-0808
Adesco S.A.
Calle 7 La Urbina Edificio Los Robles Locales C y D
Planta Baja, Caracas - Venezuela
+58-212-241-9952
Venezuela
Vietnam
Mitsubishi Electric Vietnam Co.,Ltd.
Head Office
Mitsubishi Electric Vietnam Co.,Ltd.
Hanoi Branch
Unit01-04, 10th Floor, Vincom Center, 72 Le Thanh Ton Street,
District 1, Ho Chi Minh City, Vietnam
+84-8-3910-5945
6th Floor, Detech Tower, 8 Ton That Thuyet Street,
My Dinh 2 Ward, Nam Tu Liem District, Hanoi City, Vietnam
+84-4-3937-8075
For Safety : Please read the instruction manual carefully before using the products in this catalog.
Wiring and connection must be done by the person who has specialized knowledge of
electric construction and wirings.
●Trademarks
・Microsoft, Windows Vista, Windows XP, Windows7,Windows8, Excel are U.S. registered trademark in the U.S. of U.S.
Microsoft Corporation,and other countries.