SL96C
LAMP SYNCHROSCOPE
Temperature:
Weight:
Front protection:
LAMP Synchronoscope for synchronising monitoring
•
Lamp dim indication at the “in phase” condition
Description
Specifications
Monitored Voltage:
•
50-150 or 200-500VAC
40-70Hz (Fuse 2A)
-20 to +70ºC
0.3kgs
IP52 (IP65 optional)
This DIN96 unit is a three lamp synchronoscope arranged to give lamp dim indication at the “in
phase“ condition. When the phase of busbar and incoming voltages are in coincidence, the lamp
located at 12 o'clock position will be out, and the remaining two lamps will be lit.
Direction of lamp “rotation” pattern indicates if incoming generator is TOO SLOW (-) or TOO FAST (+)
relative to busbar supply.
The unit is rated for continuous operation and may be left permanently connected to the two supplies
after synchronisation.
It must be connected to the two supplies in strict accordance with the phase sequence (L1,L2,L3) shown.
Dimensions
There are no commissioning adjustments necessary.
DIN96
PANEL
CUTOUT
92 x 92mm
1.25 to 8mm
thick
Reference
(BUSBAR)
Supply
R
R
S
S
T
T
N
N
Synchronising
(GENERATOR)
Supply
85mm
1
2
3
4
5
6
SL96C
The unit meets IEC60092-504 and the relevant environmental and EMC tests
specified in IEC60068/60092 and IEC61000/60533 respectively, to comply with the
requirements of the major Classification Societies.
The MEGACON policy is one of
co ntinuo us impro vemen t,
consequently equipment supplied
may vary in detail from this
publication.
ORDERING EXAMPLE:
Type
Monitored Voltage
: SL96C
: 200-500VAC
Norway
Denmark
United Kingdom
www.megacon.com
ELECTRONIC CONTROL AND INSTRUMENTATION
REF: Datasheet.SL96C - REV: 1.01/01.2016
© All rights reserved to Megacon
Megacon reserves the right to make any changes to the information at any time
×